Output 4–20 MA / 20–4 MA (isolated On 4-wire)
Accuracy ±0.1% Of Max Range (lab), ±0.25% Of Max Range (field)
Click to view more

Product Details

Power Supply
24V DC (±10%)
Type
Radar Level Transmitter
Features
Self-adjusting Tracking Radar Technology, Simple Push-button Calibration, 4–20 MA / 20–4 MA Output, Diagnostics And Data Logging Software, PLC Compatible, Two-wire Or Four-wire Operation, Fully Programmable, Suitable For Liquids, Solids, Tanks, Silos,
Enclosure Material
Stainless Steel (94V0)
Ingress Protection
NEMA 4 / 4X (IP67)
Installation Category
Class II
Temperature Limits
PP Rod: -40 To +190°F, PTFE Rod: -40 To +350°F
Maximum Pressure
3 Bar
Operation Principle
Pulse Radar (26 GHz)
Transmitter Power
50 µW Average
Calibration
Via Communication Port
Display
LCD

ELTAR-20 Radar Level Transmitter Features

Self-adjusting tracking radar technology
Simple push-button calibration
4–20 mA / 20–4 mA output (isolated on 4-wire models)
Diagnostics and data logging software
PLC compatible (MODBUS RTU)
Two-wire or four-wire operation
Fully programmable
Suitable for liquids, solids, tanks, silos, and reactors

Description

Electronet ELTAR-20 is a high-frequency radar level transmitter designed for accurate and reliable level measurement in industrial applications. It supports a measuring distance of up to 30 meters. Its optimized antenna and advanced microprocessor provide superior signal analysis, making it suitable for reactors, solid silos, and complex environments with steam, dust, or turbulence.

Technical Specifications Electrical & Enclosure

Electrical Connection: ½" NPT (F) × 2, M20 × 1.5 (F)
Enclosure Material: Aluminum or Stainless Steel (94V0)
Ingress Protection: NEMA 4 / 4X (IP67)
Installation Category: Class II

Operating Conditions

Temperature Limits:
• PP Rod: –40 to +190°F (–4 to +88°C)
• PTFE Rod: –40 to +350°F (–40 to +177°C)
Maximum Pressure: 3 bar
Operation Principle: Pulse Radar (26 GHz)

Electrical Specifications

Power Supply:
• 24V DC (±10%)
• 24V DC two-wire loop powered
Transmitter Power: 50 µW average
Accuracy:
• ±0.1% of max range (lab)
• ±0.25% of max range (field)
Outputs: 4–20 mA / 20–4 mA (isolated on 4-wire)
Communication: MODBUS RTU

Calibration & Diagnostics

Calibration: Via communication port
Diagnostics: Echo profile available via communication port

Antenna & Construction

Antenna Options:
• PTFE dielectric rod
• SS316 horn antenna for low dielectric materials
Probe Material: PP / PTFE / SS316 depending on antenna type

Local Indication

 

Display: LCD